NEC 2023 · Section 210.52

NEC 210.52 — Dwelling Receptacle Outlet Placement

Where 125V, 15A and 20A receptacle outlets are required in dwelling units. These are the spacing rules behind rough-in layout — and the ones inspectors walk the walls checking.

Requirements by Area

Paraphrased summary of the placement rules — verify details and exceptions in your codebook.

AreaPlacement Rule
General wall space — 210.52(A)No point along the floor line of any wall more than 6 ft from a receptacle — so receptacles land at most 12 ft apart. Any wall space 2 ft or wider counts.
Kitchen wall countertops — 210.52(C)(1)Every wall counter space 12 in. or wider gets a receptacle; no point along the wall line more than 24 in. from one (max 4 ft spacing).
Islands & peninsulas — 210.52(C)(2)NEC 2023 no longer requires a receptacle. If one is installed, it must be on or above the countertop surface, or below it only under the specific conditions in 210.52(C)(3).
Bathrooms — 210.52(D)At least one receptacle within 3 ft of the outside edge of each basin, on a wall or partition adjacent to the basin (or in/on the counter).
Outdoors — 210.52(E)One- and two-family dwellings: a receptacle at the front and back, not more than 6½ ft above grade. Balconies, decks, and porches accessible from inside also need one.
Laundry — 210.52(F)At least one receptacle for laundry equipment.
Garages — 210.52(G)(1)At least one receptacle in each vehicle bay, not more than 5½ ft above the floor.
Basements — 210.52(G)(3)At least one receptacle in each separate unfinished portion.
Hallways — 210.52(H)Hallways 10 ft or longer need at least one receptacle.
Foyers — 210.52(I)Foyers over 60 sq ft: a receptacle on each wall space 3 ft or wider.

Field Notes

  • • The 6-ft rule exists so no cord has to stretch more than 6 ft — measure along the wall line, around corners, counting doorways as breaks in wall space.
  • • Fixed room dividers and railings count as wall space; sliding-panel space counts too.
  • • Floor receptacles count toward the wall spacing only if within 18 in. of the wall.
  • • Required dwelling receptacles in most of these areas also carry AFCI (210.12), GFCI (210.8), and tamper-resistance (406.12) obligations — placement is only half the inspection.
  • • Kitchen and dining receptacles ride on at least two 20A small-appliance circuits (210.11(C)(1)); bathroom receptacles need their own 20A circuit (210.11(C)(3)).

Laying out a rough-in and hit an odd wall?

Describe the room to ElectricAI — dimensions, openings, counters — and get a cited NEC 210.52 answer in under a minute.

Ask ElectricAI Free →

Numerical values sourced from NEC 2023. For official code, refer to NFPA 70 (National Electrical Code). Always verify citations in your codebook and with your AHJ.

Not affiliated with NFPA. NEC is a registered trademark of the National Fire Protection Association.

NEC Tables · Calculators · Free Trial