NEC 2023

Table 314.16(A) — Standard Metal Box Volumes

Interior cubic-inch volumes for standard metal outlet boxes. Use these values when verifying box fill per NEC Section 314.16.

Box DescriptionVolume (in³)
4×1-1/4 square18.0
4×1-1/2 square21.0
4×2-1/8 square30.3
4×4×1-1/2 square(4-11/16 in. square)42.0
3×2×2 device10.5
3×2×2-1/4 device12.5
3×2×2-1/2 device14.0
3×2×2-3/4 device15.5
3×2×3-1/2 device18.0

Table 314.16(B)(1) — Volume per Conductor

Each conductor that enters the box counts as one volume allowance. Conductors that originate and terminate inside the box do not add additional volume.

Conductor SizeVolume per Conductor (in³)
#18 AWG1.50
#16 AWG1.75
#14 AWG2.00
#12 AWG2.25
#10 AWG2.50
#8 AWG3.00
#6 AWG5.00

Reference: NEC 2023 Section 314.16, Table 314.16(A) and Table 314.16(B)(1). Clamps, support fittings, and devices each require additional volume allowances per 314.16(B)(2)–(5). Listed nonmetallic boxes are marked with their cubic-inch volume.

Numerical values sourced from NEC 2023. For official code, refer to NFPA 70 (National Electrical Code). Always verify citations in your codebook and with your AHJ.

Not affiliated with NFPA. NEC is a registered trademark of the National Fire Protection Association.