NEC 2023 · Article 358

NEC Article 358 — Electrical Metallic Tubing (EMT)

The commercial workhorse raceway: where it's allowed, how many conductors it takes, and how it has to be strapped. Fill counts below assume all conductors are the same size.

THHN/THWN Conductor Fill (40% — 3 or More Conductors)

Selected counts for the most common trade sizes, per the Chapter 9, Table 1 fill limits (Annex C values). Mixed conductor sizes require the full calculation — use the conduit fill reference.

EMT Trade Size14 AWG12 AWG10 AWG8 AWG
1/2"12953
3/4"2216106
1"3526169

Fill is a physical limit, not an electrical one — more than 3 current-carrying conductors triggers ampacity adjustment under 310.15(C)(1).

Uses Permitted & Not Permitted — 358.10 / 358.12

  • Permitted: exposed and concealed work; wet locations with corrosion-resistant hardware and listed raintight fittings; in concrete or direct contact with earth where protected against corrosion and judged suitable.
  • Not permitted: where subject to severe physical damage; for support of luminaires or equipment (except where the tubing is identified for it); in most corrosive/cinder-fill environments without protection.
  • No threading: EMT is never threaded — couplings and connectors only. Set-screw for dry, compression rated raintight for wet.
  • Bends — 358.26: maximum 360° of bends (four quarter bends) between pull points.

358.30 — Securing & Supporting

  • • Strap within 3 ft of every box, cabinet, conduit body, or other termination.
  • • Support at intervals not exceeding 10 ft along the run.
  • • Up to 5 ft from a termination is allowed where structural members prevent fastening at 3 ft.
  • • Unbroken lengths may be fished into concealed spaces of finished buildings without securing.
  • • EMT is an equipment grounding conductor when fittings are made up tight (250.118) — every loose set-screw is a broken ground path.

Mixed conductor sizes in one run?

Tell ElectricAI what's going in the pipe — it runs the fill calculation and cites the table rows in under a minute.

Ask ElectricAI Free →

Numerical values sourced from NEC 2023. For official code, refer to NFPA 70 (National Electrical Code). Always verify citations in your codebook and with your AHJ.

Not affiliated with NFPA. NEC is a registered trademark of the National Fire Protection Association.

NEC Tables · Calculators · Free Trial