NEC 2023 · Sections 404.2(C) & 404.9(B)

NEC 404.2(C) — Neutral at Switch Locations

The end of the old two-wire switch loop. Smart switches, dimmers, and occupancy sensors need a neutral to power their electronics — so the code makes you land one at the switch box up front instead of stealing the ground for it later.

Where the Neutral Is Required

  • • Switches controlling lighting loads supplied by a grounded general-purpose branch circuit.
  • • In habitable rooms and bathrooms of dwellings, and other locations per the section's scope.
  • • The neutral doesn't have to be spliced to anything — it just has to be present in the box (capped is fine) so a future device can use it.
  • • Where multiple switch locations control the same lighting, at least one location must have the neutral.

The Exceptions That Matter in the Field

  • Raceway jobs: if the conductors arrive in a raceway big enough to pull a neutral in later, you don't need to land one now.
  • Accessible framing: cable entering through a framing cavity open at the top or bottom on the same floor — or through a wall unfinished on one side — is exempt, because the neutral can be fished later.
  • Switch loops in old work: a rewireable path is the test. If adding a neutral later means opening drywall, the neutral goes in now.
  • • Using the equipment grounding conductor as a return path for an electronic switch is never permitted — that's exactly the practice this rule exists to kill.

404.9(B) — Switch & Faceplate Grounding

  • • Snap switches and dimmers connect to the equipment grounding conductor; metal faceplates must end up grounded through the yoke.
  • • Metal boxes with proper bonding satisfy this through the mounting screws to a self-grounding yoke; nonmetallic boxes need the EGC landed on the switch's green screw.
  • • Replacement in an old box with no grounding means: GFCI protection or a nonmetallic faceplate arrangement is the permitted fallback.
  • • Related: switches must be accessible, with the operating handle's center grip no higher than 6 ft 7 in. (404.8(A)).

Old-work switch box with no neutral and a smart-switch request?

Describe the box, the cable route, and the wall to ElectricAI — get a cited 404.2(C) answer on whether the exception applies.

Ask ElectricAI Free →

Numerical values sourced from NEC 2023. For official code, refer to NFPA 70 (National Electrical Code). Always verify citations in your codebook and with your AHJ.

Not affiliated with NFPA. NEC is a registered trademark of the National Fire Protection Association.

NEC Tables · Calculators · Free Trial