NEC 2023 · Article 430

NEC Article 430 — Motors, Motor Circuits, and Controllers

Article 430 governs the installation and protection of motors, motor branch circuits, motor feeders, motor controllers, and disconnecting means. This page covers the most common field questions: conductor sizing, overload protection, and short-circuit / ground-fault protection (SCPD) sizing.

Use Table FLC, Not Nameplate FLA

For conductor and SCPD sizing, NEC 430.6(A) requires using the full-load current values from Tables 430.248, 430.249, or 430.250 — not the actual nameplate FLA. Use nameplate FLA only when sizing overload protection (Section 430.32).

Branch-Circuit Conductor Sizing

ApplicationRule
Single motor, continuous duty125% of full-load current (FLC) — NEC 430.22(A)
Motor used in short-time, intermittent, or varying dutyPercentage of FLC per Table 430.22(E) depending on duty cycle
Several motors on same circuit125% of largest motor FLC + 100% of remaining motors — NEC 430.24
Motor feeder conductors125% of largest motor + sum of other motor FLCs — NEC 430.24

Overload Protection (430.32)

Device / Motor TypeRule
Separate overload device (Class 10–20)≤ 125% of motor FLA for motors with marked service factor ≥ 1.15 or temp rise ≤ 40°C; ≤ 115% otherwise — NEC 430.32(A)(1)
Integral thermal protectorListed and marked as provided; manufacturer rating applies
SCPD when no separate overloadAllowable for hermetically sealed motors with specific marking — see 430.32(A)(2)

SCPD Sizing — Maximum Percentages (Table 430.52)

Maximum rating of the short-circuit and ground-fault protection device (SCPD) as a percentage of motor FLC (from Tables 430.248–430.250). These are maximums — you can always go smaller.

Motor TypeInverse Time BreakerDual-Element Fuse
Single-phase, all types250%175%
AC polyphase (squirrel cage, other than Design B)250%175%
Design B energy-efficient (> 30 HP)250%175%
Wound rotor150%150%
Direct current150%150%
Reluctance synchronous (high reactance)200%150%

Disconnecting Means (430.102)

  • • Required for each motor and controller.
  • • Must be within sight of the motor location and within sight of the controller — or the controller shall be capable of being locked in the open position.
  • • Must be rated in horsepower or amperes equal to or greater than the motor.
  • • Must open all ungrounded supply conductors.

Need a motor circuit sized right now?

ElectricAI can size conductors, overloads, and SCPD for any motor — just give the HP, voltage, and phase.

Size a Motor Circuit Free →