NEC 2023 · Article 625

NEC Article 625 — EV Charger Circuit Requirements

Electric vehicle supply equipment (EVSE) is a continuous load with its own article. These are the circuit-sizing, GFCI, and disconnect rules for the installs that are showing up on every residential work order.

Common Charger-to-Circuit Pairings (125% Rule)

EVSE is a continuous load — size the overcurrent device and conductors at 125% of the charger's maximum current. Copper sizes shown assume 75°C terminations and no derating; adjust for your conditions of use.

Charger OutputMin. Circuit / BreakerTypical Copper
16A charger (3.8 kW @ 240V)20A12 AWG Cu
24A charger (5.8 kW)30A10 AWG Cu
32A charger (7.7 kW)40A8 AWG Cu
40A charger (9.6 kW)50A8 AWG Cu (75°C)
48A charger (11.5 kW)60A6 AWG Cu (75°C)

The Rules That Get Cited

  • Dedicated circuit — 625.40: each outlet installed for EV charging gets an individual branch circuit with no other outlets. Exception: loads controlled by an energy management system per 625.42.
  • Load management — 625.42: an EMS or the EVSE's own adjustable current setting can set the calculated load — how panel-constrained houses get a charger without a service upgrade. If adjustable, the setting method must be restricted (tool, password, or similar).
  • GFCI — 625.54: receptacles installed for EV power transfer require GFCI protection. That includes the NEMA 14-50 behind a plug-in charger.
  • Disconnect — 625.43: hardwired equipment rated over 60A or over 150V to ground needs a disconnecting means in a readily accessible location, in sight of the equipment, and lockable open.
  • Service capacity: run an Article 220 load calculation before adding a 48A charger to an existing dwelling — the charger alone adds 11.5 kW of continuous load unless managed.

Field Notes

  • • Hardwiring a 48A-capable charger avoids both the receptacle GFCI (nuisance-trip complaints) and the 50A receptacle cap — most manufacturers require hardwiring above 40A output.
  • • Many chargers ship with adjustable output: a "60A" unit set to 40A can legally ride a 50A circuit — document the setting.
  • • Check the terminal temperature rating on the EVSE — some are 60°C, which changes the conductor size.
  • • Local energy codes and utility EV programs may add metering or load-management requirements on top of the NEC.

Quoting an EV charger install this week?

Give ElectricAI the panel size, existing loads, and charger model — get a cited Article 625 answer and load-calc help in under a minute.

Ask ElectricAI Free →

Numerical values sourced from NEC 2023. For official code, refer to NFPA 70 (National Electrical Code). Always verify citations in your codebook and with your AHJ.

Not affiliated with NFPA. NEC is a registered trademark of the National Fire Protection Association.

NEC Tables · Calculators · Free Trial